Review No:1 Central Fire Dept.
4001
Permit:
We have reviewed plans for the above subject project. THE PLANS HAVE BEEN DENIED.
Please have the DESIGNER add appropriate NOTES and DETAILS showing this information and RESUBMIT plans, VIA COUNTY, with an annotated copy of this letter.
NOTE The FDC/PIV shall be labeled with the address of the building that it serves, with 2” peal and stick plastic reflective numbers.
NOTE on the plans that the designer/installer shall submit two (2) sets of plans and cut sheets for the automatic sprinkler system to this agency for approval. Cut sheets shall include, but not limited to piping, valves, gauges, and sprinkler heads.
NOTE on the plans that a current five year certification is to be provided to the fire inspector prior to the final building inspection.
SHOW location of exit signs.
SHOW where address numbers will be posted and maintained, plainly visible from the street. Numbers shall be a minimum of four (4) inches in height and of a color contrasting to their background.
SHOW location of Knox Box and key.
NOTE roof coverings to be no less than Class "B" rated roof.
The job copies of the building and fire systems plans and permits must be on-site during inspections.
If you should have any questions regarding the plan check comments, please call me at (831) 479-6843 and leave a message, or email me at tomw@centralfpd.com. All other questions may be directed to Fire Prevention at (831)479-6843.
CC: File & County
As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source. Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the Central FPD of Santa Cruz County.
4001-062411
Review No:2Central Fire
4001
Permit: 20110125
Based upon a review of the plans submitted, District requirements appear to have been met, and PLANS ARE APPROVED FOR PERMIT.
The job copies of the building and fire system plans and permits must be on-site during inspection.
Submit a check in the amount of $ 288.80 for this particular plan check, made payable to Central Fire Protection District. INVOICE MAILED TO APPLICANT. Other fees may be incurred. Please contact the Fire Prevention Secretary for total fees due for your project. Fire District fees must be paid and a receipt for District fees must be presented to the County Planning Department before Building Permit issuance.
Upon completion of the above listed requirements please call the Fire Prevention Division to set up an appointment for an inspection. You will be asked for an address and Assessors Parcel Number (APN). A MINIMUM OF 48 HOURS NOTICE to the fire department is required prior to inspection.
If you should have any questions regarding the plan check comments, please call me at (831) 479-6843 and leave a message, or email me at tomw@centralfpd.com. All other questions may be directed to Fire Prevention at (831)479-6843.
CC: File
As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source. Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the Central FPD of Santa Cruz County.
4001-072111
|