Review No:1 1. Please include room area uses on the floor plans.
2. Please include all counters to be installed as part of this permit. Dimension counter heights and maneuvering clearances around counters and other fixed equipment, and specify the counter functions. Accessible counters shall be provided for each function (i.e. cashier area and work surfaces for the public). Such accessible counters shall be 36" long and between 28" and 34" above finish floor. CBC 1122B
3. Please provide suspended ceiling installation details to comply with ASTM C635 and ASTM C636. Also, structural requirements for ceiling system and fixture support shall be detailed to comply with ASCE 7-05, 13.5.6.2.2. Include connections to the trusses above.
4. Please correct the wall finish note on A-1. It appears 1/2" GYP should be specified, rather than S1#2;" GAP.