Fire Review

Review No:1

Date:              September 18, 2014

To:                   Bei-Scott Company

Applicant:  SAME

From:              Jim Dias

Subject:         TI

Address:        4101 Soquel Dr  B-1   Soquel  CA  95073

APN:               030-061-28

OCC:               4024

Permit:       B-143666

 

We have reviewed plans for the above subject project.  THE PLANS HAVE BEEN DENIED.

 

Please have the DESIGNER add appropriate NOTES and DETAILS showing this information and RESUBMIT plans, VIA COUNTY, with an annotated copy of this letter.

 

NOTE on the plans that the designer/installer shall submit two (2) sets of plans, calculations, and cut sheets for the automatic hood & duct fire suppression system to this agency for approval. 

 

NOTE on the plans that the automatic hood & duct fire suppression system shall be tied into the building fire alarm system to notify of any discharges.

 

NOTE on the plans the hood and duct fire extinguishing system is to be in compliance with U.L. 300 standards.

 

SHOW the location of the “K” fire extinguisher on the plans within 35 feet of all cooking equipment that is protected by the extinguishing system(s).

 

SHOW location of fire extinguishers.

 

SHOW Occupant Load(s) and an Exiting Plan.

 

SHOW location of exit signs.

 

SHOW location of Knox Box and key.

 

The job copies of the building and fire systems plans and permits must be on-site during inspections.

 

If you should have any questions regarding the plan check comments, please call me at (831) 479-6843 and leave a message, or email me at jimd@csgengr.com .  All other questions may be directed to Fire Prevention at (831)479-6843.

 

CC:  File & County

 

As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source.  Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the Central FPD of Santa Cruz County.

Review No:2

Date:              October 30, 2014

To:                   Bei-Scott Company

Applicant:   SAME

From:              Jim Dias

Subject:            TI to existing Commercial Building

Address:           4101 Soquel Dr  B-1  Soquel  CA  95073

APN:               030-061-28

OCC:               4024

Permit:         B-143666

 

Based upon a review of the plans submitted, District requirements appear to have been met, and PLANS ARE APPROVED FOR PERMIT.

 

The job copies of the building and fire system plans and permits must be on-site during inspection.

 

Upon completion of the above listed requirements please call the Fire Prevention Division to set up an appointment for an inspection.  You will be asked for an address and Assessors Parcel Number (APN).  A MINIMUM OF 48 HOURS NOTICE to the fire department is required prior to inspection.

 

Submit a check in the amount of $450.40 for this particular plan check, made payable to Central Fire Protection District.  INVOICE MAILED TO OWNER OF RECORD.  Other fees may be incurred.  Please contact the Fire Prevention Secretary for total fees due for your project.  Fire District fees must be paid and a receipt for District fees must be presented to the County Planning Department before Building Permit issuance.

If you should have any questions regarding the plan check comments, please call me at (831) 479-6843 and leave a message, or email me at jimd@csgengr.com.  All other questions may be directed to Fire Prevention at (831)479-6843.

 

CC:  File

As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source.  Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the Central FPD of Santa Cruz County.