Fire Review

Review No:1

Date:                 July 7, 2016

To:                    Mainstreet Trio LLC

Applicant:      SAME

From:                Jim Dias

Subject: New Wine Bar in an existing commercial occupancy

Address:                4901 Soquel Dr   Soquel CA  95073

APN:                 030-094-18

OCC:                 1562    

Permit:           B-163011      

 

We have reviewed plans for the above subject project.  THE PLANS HAVE BEEN DENIED.

 

Please have the DESIGNER add appropriate NOTES and DETAILS showing this information and RESUBMIT plans, VIA COUNTY, with an annotated copy of this letter.

 

NOTE on the plans that these plans are in compliance with California Building and Fire Codes (2013) as amended by the Central Fire Protection District.

 

NOTE on the plans the occupancy classification as determined by the building official and outlined in Part III of the California Building Code.

 

NOTE on the plans occupancy load of each area. Show where occupancy control signs will be posted.  Appears that the occupant load for this plan is understated because not all areas appear to have been properly accounted for and the proper occupant load factors were not utilized.  Also there are two different occupancy load analysis’ which differ greatly.

 

SHOW location of fire extinguishers.

 

SHOW Occupant Load(s) and an Exiting Plan.

 

SHOW location of exit signs.

 

SHOW where the address numbers will be posted and maintained, plainly visible from the street.  Numbers shall be a minimum of six (6) inches in height and of a color contrasting to their background.

 

SHOW location of Knox Box and key.

 

NOTE roof coverings to be no less than Class "B" rated roof.

 

The job copies of the building and fire systems plans and permits must be on-site during inspections.

 

If you should have any questions regarding the plan check comments, please call me at (831) 479-6843 and leave a message, or email me at jimd@centralfpd.com.  All other questions may be directed to Fire Prevention at (831)479-6843.

 

CC:  File & County

 

As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source.  Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the Central FPD of Santa Cruz County.

Review No:2

Date:                 October 13, 2016

To:                    Mainstreet Trio LLC

Applicant:      SAME

From:                Jim Dias

Subject: New Wine Bar in an existing commercial occupancy

Address:                4901 Soquel Dr   Soquel CA  95073

APN:                 030-094-18

OCC:                 1562   

Permit:           B-163011      

 

Based upon a review of the plans submitted, District requirements appear to have been met, and PLANS ARE APPROVED FOR PERMIT.

 

The job copies of the building and fire system plans and permits must be on-site during inspection.

 

Submit a check in the amount of $ 468.80 for this particular plan check, made payable to Central Fire Protection District.  INVOICE MAILED TO OWNER OF RECORD.  Other fees may be incurred.  Please contact the Fire Prevention Secretary for total fees due for your project.  Fire District fees must be paid and a receipt for District fees must be presented to the County Planning Department before Building Permit issuance.

 

Upon completion of the above listed requirements please call the Fire Prevention Division to set up an appointment for an inspection.  You will be asked for an address and Assessors Parcel Number (APN).  A MINIMUM OF 48 HOURS NOTICE to the fire department is required prior to inspection.

 

If you should have any questions regarding the plan check comments, please call me at (831) 479-6843 and leave a message, or email me at jimd@csgengr.com .  All other questions may be directed to Fire Prevention at (831)479-6843.

 

CC:  File

As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source.  Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the Central FPD of Santa Cruz County.