Fire Review |
|
Date: March 23, 2018
To: Barry Swenson Builders – c/o Aaron Hosmer
Applicant: SAME
From: Jim Dias
Subject: Mixed use development
Address 1155 17th Ave Santa Cruz CA 95062
APN: 026-311-330
OCC: 2451
Permit: B-181279
We have reviewed plans for the above subject project. THE PLANS HAVE BEEN DENIED.
Please have the DESIGNER add appropriate NOTES and DETAILS showing this information and RESUBMIT plans, VIA COUNTY, with an annotated copy of this letter.
ADD NOTE on the plans that these plans are in compliance with California Building and Fire Codes (2010) as amended by the Central Fire Protection District.
ADD NOTE The FDC shall be labeled with the address of the building that it serves, with 2” peal and stick plastic reflective numbers.
ADD NOTE on the plans that the designer/installer shall submit two (2) sets of plans, calculations, and cut sheets for the automatic sprinkler system to this agency for approval. Cut sheets shall include, but not limited to piping, valves, gauges, and sprinkler heads.
ADD NOTE on the plans “All inspector test valves and drain valves must drain to sanitary sewer, oil sand separator, or bio swale. At no time may any of these valves drain to the storm drain system.”
ADD NOTE on the plans that the designer/installer shall submit a minimum of two (2) sets of plans, battery calculations, and cut sheets and CSFM listings for the automatic fire alarm equipment and appurtenances to this agency for approval.
ADD NOTE for fire alarm control unit placement. Best location will be in the Electrical / MPOE room.
ADD NOTE - Occupant notification (mini horns) shall be installed in each residential unit. ADA unit shall be equipped with ADA compliant notification appliances (audio/visual).
ADD a fire extinguisher to the Electrical / MPOE room.
SHOW where the address numbers will be posted and maintained, plainly visible from the street.
ADD NOTE to plans that assigned street address number shall be a minimum of 6” in height and of a color contrasting to their background.
ADD NOTE to plans that assigned suite numbers shall be a minimum of 4” in height and of a color contrasting to their background. Consult with Central Fire District for best location(s) to place. ALL suites with front and rear entrance/access shall have numbers at each door.
SHOW location of KNOX Key Box. The best location will be on the end of the building close to the Electrical / MPOE room.
CORRECT DRAWINGS - A separate tap is required for the new fire hydrant and the fire service. Incorrect installation is shown on pages C4, C5, C6 and C11.
CORRECT DRAWINGS - Use the correct hydrant detail. Please refer to the City of Santa Cruz Water Department’s Standard Detail 10.
ADD the correct detail for the fire service backflow equipment. Please refer to the City of Santa Cruz Water Department’s Standard Detail 9.
ADD NOTE on page M-1 that duct smoke detector will be required for AC-1 (>/=2000 cfm).
ADD NOTE The job copies of the building and fire systems plans and permits must be on-site during inspections.
If you should have any questions regarding the plan check comments, please call me at (831) 479-6843 and leave a message, or email me at jimd@centralfpd.com. All other questions may be directed to Fire Prevention at (831)479-6843.
CC: File & County
As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source. Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the Central FPD of Santa Cruz County.
Date: May 25, 2018 To: Green Valley Corporation Applicant: SAME From: Jim Dias Subject: 2
story Multi-use structure Address: SW
Corner of Brommer & 17th Ave
Santa Cruz CA 95062 APN: 026-311-33 OCC: 2451 Permit: B-181279
Based upon a
review of the plans submitted, District requirements appear to have been met,
and PLANS ARE APPROVED FOR PERMIT.
The job copies of the building and fire system plans and
permits must be on-site during inspection.
Upon completion
of the above listed requirements please call the Fire Prevention Division to
set up an appointment for an inspection.
You will be asked for an address and Assessors Parcel Number (APN). A
MINIMUM OF 48 HOURS NOTICE to the fire department is required prior to
inspection.
Submit a check in
the amount of $9,201.60 for this particular plan check, made payable to Central Fire Protection
District. INVOICE MAILED TO OWNER OF
RECORD. Other fees may be incurred. Please contact the Fire Prevention Secretary
for total fees due for your project.
Fire District fees must be paid and a receipt for District fees must be
presented to the County Planning Department before Building Permit issuance. If you should
have any questions regarding the plan check comments, please call me at (831) 479-6843
and leave a message, or email me at jimd@csgengr.com. All other questions may be directed to Fire
Prevention at (831)479-6843.
CC: File As a condition of
submittal of these plans, the submitter, designer and installer certify that
these plans and details comply with applicable Specifications, Standards, Codes
and Ordinances, agree that they are solely responsible for compliance with
applicable Specifications, Standards, Codes and Ordinances, and further agree
to correct any deficiencies noted by this review, subsequent review, inspection
or other source. Further, the submitter,
designer, and installer agrees to hold harmless from any and all alleged claims
to have arisen from any compliance deficiencies, without prejudice, the reviewer
and the Central FPD of Santa Cruz County.
|