Building Review

Review No:1

1. Please include daylit zones on the lighting plans and specify separate switching and automatic daylighting controls for this lighting on the plans, sheet E2. [CA Energy Section 130.1 (d)]



2. Please revise the lighting fixture schedule for Fixture A on Sheet E2 and coordinate this with the energy compliance documents. The description is for LED’s, but the lamp information represents 2 fluorescent lamps of 32 watts each. The energy documents show 55 watts per fixture type A.



3. Please include dimmer and occupancy controls for lighting on Sheet E2 that correspond with the areas specified on the energy compliance documents.



4. Please specify testing for ventilation air on the mechanical plans. [CA Energy Section 120.5(a)1].


Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. Have changes made to the plans not resulting from this correction list?


Please check ____________Yes ______________No


If Yes, please describe the changes and where they are located in the plans:


Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx .


For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx


Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate.