1. Please clarify the type and number of bolted connections for the logo sign, letters and attribute wall sign. For the logo and letters, the structural calculations use 4 bolts each, 3/8"x 16 SS bolts. For the attribute wall sign, the structural calculations use 2 rows of 8 bolts, 3/8"-16 6061-T6 aluminum bolts.
2. Please submit energy compliance documents for sign lighting and corresponding controls. Include requirements on the drawings. [CA Energy Std. 130.3, 140.8]
3. Please locate the canopy sign such that it does not hang over a walkway without having a minimum headroom clearance of 6'8" (80 inches). [CBC 11B-307.4]
Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. Have changes made to the plans not resulting from this correction list?
Please check ____________Yes ______________No
If Yes, please describe the changes and where they are located in the plans: