1. The west wall has new openings that will reduce the lateral resistance along this wall line for shear walls. Please have the engineer of record provide analysis, based on the shear resistive construction available along this wall line. Revise the plans for any required lateral load resistive construction.
2. Please provide energy compliance documents for the revised envelope due to changes in openings at exterior walls. Requirements developed in the energy documents need to be identified in the plan sets.
Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. Have changes made to the plans not resulting from this correction list?
Please check ____________Yes ______________No
If Yes, please describe the changes and where they are located in the plans:
Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx .
For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx