1. Please specify the previous permitted use and occupancy of the tenant space.
2. Please specify the occupancy of the adjacent spaces. State whether or not the occupancies are separated per CBC 508.1 or non-separated per CBC 508.3.
3. Please provide building code information to include the allowable area of the building, based on separated or non-separated occupancies. Identify existing or new fire walls or fire barriers. For new fire-resistive construction, provide complete details and specifications.
4. The required second exit needs to have a tactile with Braille exit sign. Please include this specification on A2.0.
5. Please provide ramp and handrail details, and show the exit path to the public way or a safe dispersal area. [CBC 1028.5, 11B-405]
6. Please dimension clearances for maneuvering at the member lobby. [CBC 304]
7. Single user toilet facilities shall be identified as all-gender toilet facilities with signage to have a geometric symbol on the door that is an equilateral triangle superimposed onto a circle. This "unisex" symbol is the only specific indicator required to be provided by Chapter 11B for a toilet facility that is available for use by all individuals. No pictogram, text, or braille is required on the symbol. A "single-user toilet facility" means a toilet facility with no more than one water closet and one urinal with a locking mechanism controlled by the user. [Health & Safety Code 118600]
8. For accessible restrooms, A minimum 60 inches wide and 48 inches deep maneuvering space shall be provided in front of the water closet. The urinal encroaches into this clear space [CBC 11B-604.3.1]
9. Please revise the shower plans to comply with fully open 60" long showers for a standard roll-in showers or detail alternative roll-in showers. CBC 11B-608.2.2, 608.2.3]
10. Please include details for the high-low drinking fountain. Drinking fountains need to be located in an alcove, or detail wing walls or barriers per CBC 11B-602.9.
11. Please provide complete details for shower accessibility to include seats, grab bars and controls. [CBC 11B-608]
12. Please revise note 4 on A5.0. Maximum water flow for the water closet / toilet is 1.28 gal/flush. [CALGreen, CPC 411.2]
13. Sheet A7.0 contains notes that are non-applicable and/or relate to residential construction. Please revise notes to reference CBC requirements and delete non-applicable notes.
14. Please include structural details and specifications for the suspended ceiling seismic bracing and support. Include member sizes, types and connections. [CBC 808]
15. Please include specifications for the "C" shaped ceiling joists to include gauge and C shape sizes. Also include connections details to new and existing construction.
16. Provide header callout and details for the support of ceiling joists shown on Sheet A7.0.
17. Please specify fastener types (manufacturer and model number) for metal studs to foundation.
18. Please revise the shower fixture flow rate on A9.0 to specify 1.8 gpm at 80 psi. [CALGreen 5.303.3.3.1]
19. Please delete the non-applicable note regarding existing plumbing fixtures on A9.0, as all are new.
20. Mechanical sheets need to be signed by the CA licensed professional who prepared them. [§5536.1, 6735 California Business and Profession Code]
21. The declaration statements on energy compliance forms NRCC-MCH-04-E and NRCC-MCH-05-E need to be signed.
22. Electrical sheets need to be signed by the CA licensed professional who prepared them. [§5536.1, 6735 California Business and Profession Code]
23. The declaration statements on energy compliance forms NRCC-LTI-02-E and NRCC-ELC-01-E need to be signed.
Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. Have changes made to the plans not resulting from this correction list?
Please check ____________Yes ______________No
If Yes, please describe the changes and where they are in the plans:
Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx .
For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx