Building Review |
|
2. Please include manufacturer’s specifications for the suspended ceiling system to correspond with the requirements in the USG table on A-2.1. Include compression strut, main tee and cross tee information and connections to the roof/ceiling supports. Suspended ceiling support systems shall be approved by a responsible CA licensed engineer or architect. Otherwise, note this as a deferred submittal on the cover sheet of the drawings. The deferred submittal items shall not be installed until their design and submittal documents have been approved by the Building Official. [CBC 107.3.4.2] 3. Please include seismic restraint details and specifications for mechanical equipment to correspond with the notes on Sheet M-1. These specifications and details shall be be approved by a responsible CA licensed engineer or architect. Otherwise, note this as a deferred submittal on the cover sheet of the drawings. The deferred submittal items shall not be installed until their design and submittal documents have been approved by the Building Official. [CBC 107.3.4.2] 4. Please identify an air gap at food preparation sinks, refrigerators, refrigeration coils, freezers, walk-in coolers, iceboxes, ice-making machines, steam tables, egg boilers, coffee urns and brewers, hot-and-cold drink dispensers, and similar equipment where cross-contamination may occur. An air gap shall be not less than 1” measured from the lowest point of the indirect waste pipe to the flood-level rim of the receptor. [CPC 801] 5. Please verify the pressure drop of 1.0 psi for gas pipe sizing. If the pressure drop is less than 1.0 psi, please revise the gas pipe sizing to correspond with CPC Table 1216.2(1). Have changes made to the plans not resulting from this correction list? Please check ____________Yes ______________No If Yes, please describe the changes and where they are located in the plans: Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx . For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate. If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us. Have changes made to the plans not resulting from this correction list? Please check ____________Yes ______________No If Yes, please describe the changes and where they are located in the plans: Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx . For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate. If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us. 2. The documentation author needs to sign the declaration statement on the NRCC-PRF-01E form, pg 13 of 18 on M-7. Have changes made to the plans not resulting from this correction list? Please check ____________Yes ______________No If Yes, please describe the changes and where they are located in the plans: Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx . For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate. If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us. |