1.  Please submit energy compliance forms for sign lighting.  The documentation author and responsible designer will need to sign the declaration statement on the certificate of compliance.    [CA Energy §10-103(a)1.A.vi]  
 
2.  Please include specifications for the structural connections of the sign to the existing structure, rather than “fasteners as required”.  Include fastener type, distance into wood support and spacings.  
 
3.  The floor plan shows the location at the Aptos Nail Salon.  It appears that the sign will be at Tenant Space #64.  Please clarify.
 
 
Have changes made to the plans not resulting from this correction list?  Please check ____________Yes  ______________No   If Yes, please describe the changes and where they are located in the plans:
 
Note:  For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx  .
For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx  
Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate.  