Building Review

Review No:1
1.  The project description does not correspond with the electrical plans.  The electrical plans show demising walls that differ from the floor plans.  The electrical plans show an additional Suite 125 and there is an added electrical panel for this suite).  Please revise the project description on the change order application and/or plans.
 
 
Note:  Zoning review is required for the added Suite.  This change order was not originally routed to Zoning.  
 
Have changes made to the plans not resulting from this correction list?  Please check ____________Yes  ______________No   If Yes, please describe the changes and where they are located in the plans:
 
Note:  For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx  .
For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx   Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate.   