1.  The energy documents show a cross out of the mandatory sign lighting controls on NRCCLTS-01-E part 1b.  All outdoor sign lighting shall be controlled with a photocontrol in addition to an automatic time-switch control, or an astronomical time-switch control.  Except all outdoor sign lighting that is ON both day and night shall be controlled with a dimmer that provides the ability to automatically reduce sign lighting power by a minimum of 65 percent during nighttime hours. Signs that are illuminated at night and for more than 1 hour during daylight hours shall be considered ON both day and night. Please revise the form.  CEnC 130.3(a)2B
 
2.  Part 3 of the energy form NRCC-LTS-01-E is not complete.  Please include column D 
 
 
3.  The person responsible for the designing the lighting plan needs to sign the declaration statement on page 5 of the   NRCC-LTS-01-E form.   The plans specify Philip Bulger as the project designer.  
 
4.  Please locate and identify the electrical disconnect and grounding on the sign plan.  [CEC 600.6, 600.7]
 
Have changes made to the plans not resulting from this correction list?  Please check ____________Yes  ______________No   If Yes, please describe the changes and where they are located in the plans:
 
Note:  For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx  .
For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx  
Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate.   
If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us.