Building Review

Review No:1
1. The sign lighting general information, part 1a and 1b  on the certificate of compliance is incorrect.  This is a new sign and sign lighting shall be controlled per mandatory features in CA Energy Standard Section 130.3.   There are no existing sign lighting controls.  Please revise the Sign Lighting form NRCC-LTS-01-E.
 
2. Please identify and locate the disconnect for the sign per CEC 600.6
 
 
3. Please identify the fastener types and spacings.  Coordinate with existing construction conditions, the weight on the fasteners vs. the allowable load for the fastener type.  The weight of the sign needs to be specified.  
 
Have changes made to the plans not resulting from this correction list?    Please check ____________Yes  ______________No     If Yes, please describe the changes and where they are located in the plans:  
 
Note:  For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx  .
Resubmittal Requirements: 
1) “Complete sets” of plans with revisions clouded, labeled, and keyed to a revision date list. 
2) Written responses referencing revised sheet(s) and/or detail(s). This plan check list may be copied and responses written below each item.  
3) Supplemental documents, as required.
Resubmittal Information: http://www.sccoplanning.com/Portals/2/County/Planning/bldg/Resubmittal%20Process%207.21.16.pdf Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate.   
 
If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us.