Review No:11. The issued plans for the Rite Aid tenant improvements include mechanical plans by a different mechanical engineer of record, Joshua Enriquez. Please provide a transfer of responsibility form PLG250, located under “handouts & forms” at sccoplanning.com, or provide the existing engineer of record’s approval for the proposed change. 2. Please provide a revise roof equipment plan that locates and identifies the replacement RTU. Coordinate these plans with the issued set of plans for the tenant improvement. 3. Please include mounting specifications and details for the replacement equipment per manufacturer and existing conditions.
4. Please provide a review from the engineer or architect of record for the increased weight of the RTU and the capacity of the existing support framing.
Have changes made to the plans not resulting from this correction list? Please check ____________Yes ______________No If Yes, please describe the changes and where they are located in the plans: Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx . Resubmittal Requirements: 1) “Complete sets” of plans with revisions clouded, labeled, and keyed to a revision date list. 2) Written responses referencing revised sheet(s) and/or detail(s). This plan check list may be copied and responses written below each item. 3) Supplemental documents, as required. Resubmittal Information: http://www.sccoplanning.com/Portals/2/County/Planning/bldg/Resubmittal%20Process%207.21.16.pdf Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate. If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us.
|