Building Review

Review No:1
1. Single user toilet facilities shall be identified as all-gender toilet facilities with signage to have a geometric symbol on the door that is an equilateral triangle superimposed onto a circle.    This "unisex" symbol is the only specific indicator required to be provided by Chapter 11B for a toilet facility that is available for use by all individuals. No pictogram, text, or braille is required on the symbol.  Please revise the men’s and women’s restroom designations on Sheet A-2.0 and refer to that applicable signage.   [Health & Safety Code 118600] 
 
2.  Drinking fountains shall be in an alcove, or within wing walls such that the drinking fountain does not encroach into the pedestrian way.  The alcove or barrier shall be minimum 18” deep but shall project at least as far as the drinking fountain and to within 6” vertically from the floor.  [CBC  11B-602.9]
 
3. The hand dryers in the restrooms are shown to encroach into the clear 60” space required at the water closets.  Please show maximum 4” projection.  [CBC 11B-604.3.1, 11B307.2]
 
4. Please revise the baby changing table height above floor toe 2’10” maximum on Sheet A6.2, rather than minimum.  CBC 11B-226.4, 309, 902]
 
5. Please dimension minimum 18” strike side clearance at door #5 on A-2.0 and/or A-6.3.  [CBC 11B-404.2.4.1]  
 
6. Please include maneuvering clearances and aisle widths in the pharmacy room.  [CBC 11B-403.5]
 
7. Please reference to an accessible sink detail from the handwash sink in the pharmacy room.  [CBC 11B-212.3, 306.2.3]
 
8. Please dimension widths at the enlarged floor plan for the employee access at the hand dip and checkout counter areas on Sheet A-6.0.  [CBC 11B-403.5]
 
9. Please revise the storage rack design criteria on A-7.1 to correspond with the 2016 CBC requirements in Section 2209.  
 
10. Please include daylit zone areas on the lighting plan, A3.1A.  Revise page 3 on the NRCC-LT1-01-E form and page 2 of the NRCC-LT1-02-E form to include daylit controls.  [CA Energy Code 130.1(d)]
 
11. Please identify an air gap at food preparation sinks, refrigerators, refrigeration coils, freezers,  ice cream dipper wells, iceboxes, ice-making machines, and similar equipment where cross-contamination may occur.  An air gap shall be not less than 1” measured from the lowest point of the indirect waste pipe to the flood-level rim of the receptor.  [CPC 801]
 12. Please complete and submit two copies of a special inspection and testing agreement form for the Titen HD connections at the lintel for the CMU wall opening shown on detail 1/A7.5   This is required in the ICC Evaluation Report, ESR-1056, and this department.  This form and a list of approved special inspection agencies are available under “forms” at http://www.sccoplanning.com/PlanningHome/BuildingSafety.aspx .   [CBC 1704]
 
 
13. Please complete and submit two copies a statement of special inspection from the engineer of record.  The engineer of record may prepare his or her own statement, or use the county’s form at   http://www.sccoplanning.com/PlanningHome/BuildingSafety.aspx .    The statement shall identify the special inspector for each item that requires special inspection.    [CBC 1704]
 
Have changes made to the plans not resulting from this correction list?  Please check ____________Yes  ______________No   If Yes, please describe the changes and where they are located in the plans:
 
Note:  For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx  . For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx   Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate.   
 
If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us.
 
Review No:3
Permit has been issued. Routed in error.