Building Review

Review No:1
1. Please submit structural calculations that are stamped and signed for the stair design, using the design criteria from the project engineer and minimum live loads in CBC Table 1607.1, which is 100 psf live load and a non-concurrent 300 lb. concentrated load.  
 
2.  Please include stair stringer connection design and detailing  to support framing.  
  3. Please specify the approved fabricator for the stairs (IAS, AISC, City of LA or other approving body), or specify special inspection for shop welding will be performed. If the stair has already been fabricated and the fabricator was not approved, a special inspection agency report is required. For approved fabricator construction, a certificate of compliance is required. CBC 1704.2
  
Have changes made to the plans not resulting from this correction list?  Please check ____________Yes  ______________No   If Yes, please describe the changes and where they are located in the plans:
 
Note:  For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx  .
For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx   Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate.   
If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us.