Building Review

Review No:1
1.  There is no indication of changes made to sheet MP1.0.  The building inspector’s correction notice requests changes to the under-slab waste plumbing be submitted in the documents.  
 
2.  Revised lighting plans were not included with this submittal.  The project description includes changes to the emergency lighting.  Include revised energy compliance forms for lighting, as required by CA Energy Code.  
 
Have changes made to the plans not resulting from this correction list?  Please check ____________Yes  ______________No   If Yes, please describe the changes and where they are located in the plans:
 
Note:  For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx  .
For eplan resubmittal requirements, please see http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx   Please be advised that if plan check comments are required to be addressed leading to a 3rd plan check, additional charges will be added to your permit fee at an hourly rate.   
If you have any questions regarding these building plan check comments, please contact Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us.