Building Review |
|
2. Please specify and detail ventilation method at the enclosed rafter bays or detail and
specify method for a non-ventilated. CBC 1202.2, 1202.3
3. Please provide specifications and/or details at the intersection of the new wood wall
framing and the CMU wall.
Have changes made to the plans not resulting from this correction list?
Please check ____________Yes ______________No
If Yes, please describe the changes and where they are located in the plans:
Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx
and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx .
For eplan resubmittal requirements, please see
http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx
Please be advised that if plan check comments are required to be addressed leading to a 3rd
plan check, additional charges will be added to your permit fee at an hourly rate.