Fire Review

Review No:1

Date:              March 9, 2021

To:                   Rancho Del Mar Centers, LLC by Terramar Retail Ctrs, LLC

Applicant:   Frank Wright

Address:      1152 E. 7th.   Ontario  CA  91764

From:              Carol Wallace, Plans Examiner

Subject:         Commercial TI

Address:        150 Rancho Del Mar  Aptos  CA  95003

APN:               039-221-11 (bldg.K)                     

Permit:       B-211539

 

 

The Central Fire District has reviewed the plans for the above cited project and the following corrections are required before approval can be obtained. 

 

Please add the appropriate NOTES, DETAILS and INFORMATION on your plans and RESUBMIT with an annotated copy of this letter. All changes to drawings will require "clouding of the change".

 

CORRECT on building plan application form PLG200, the legal owner information showing Scott Grady.  A later entry on Owner Agent Authorization form PLG210, the owner and Rancho Del Mar Centers, LLC.  Correct whichever to correct owner.

 

CORRECT on plans, page G-001, Required Agency Approvals, from City of Aptos to Aptos/La Selva Fire Protection District.

 

ADD to plans, page G-001, Applicable Codes, and 2019 Aptos/La Selva Fire Protection District Local Amendments.

 

NOTE on plans, page G-001 Deferred Submittals, that modifications to the existing fire alarm system shall be deferred submittal.  Aptos/La Selva Fire Protection District Ordinance 1-19 requires a monitored fire alarm system in all commercial structures.

 

NOTE on plans, page G-001, that prior to making any alterations on the fire alarm system, plans must be submitted for approval and permit issued.

 

NOTE on the plans “the designer/installer shall submit two (2) sets of plans and calculations for the Fire Alarm System to this agency for approval.” 

 

IDENTIFY in the legend, or call out on plan, page A-301, the symbol for the fire extinguisher.  The extinguisher symbol shown is not identified in a legend that I found.

 

CORRECT on the plans, page G-001, that address numbers shall be a minimum of 6 inches, not 4 inches.

 

CORRECT on plans, page G-003, Door Notes, #2 rear address note referring to Long Beach Airport, and the reference to City of Aptos to Aptos/La Selva Fire Protection District

 

REMOVE on plans, page G-003, Door Notes, #2 reference to multi-tenant bldgs. Not applicable to this plan submittal.

 

REMOVE on plans, page G-003, Door Notes, #4 reference to the Long Beach Muni Code (LBMC section….)

 

NOTE on the plans” the job copies of the building and fire systems plans and permits must be on-site during inspections.”

 

Note:  As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source, and, to hold harmless and without prejudice, the reviewer and reviewing agency.

Review No:2

Date:              May 11, 2021

To:                   Rancho Del Mar Centers, LLC by Terramar Retail Ctrs, LLC

Applicant:   Frank Wright

Address:      1152 E. 7th.   Ontario  CA  91764

From:              Carol Wallace, Plans Examiner

Subject:         Commercial TI

Address:        150 Rancho Del Mar  Aptos  CA  95003

APN:               039-221-11 (bldg.K)                     

Permit:       B-211539

                       

 

Based upon a review of the plans submitted, District requirements appear to have been met, and

PLANS ARE APPROVED FOR PERMIT.

 

The job copies of the building and fire system plans and permits must be on-site during inspection.

 

Please call the Community Risk Reduction Division to set up an appointment when ready for an inspection. You will be asked for an address and Assessor’s Parcel Number (APN).  A MINIMUM OF 48 HOURS NOTICE to the Fire District is required prior to inspection.

 

Submit a check in the amount of $600.00 for this particular plan check, made payable to Aptos Fire Protection District.

 

Mail to:  Community Risk Reduction

                6934 Soquel Drive, Aptos, CA 95003

 

Fire District fees must be paid and a receipt for District fees must be presented to the County Planning Department before Building Permit issuance. A $75.00 late fee may be added to your plan check fees if payment is not received within 30 days of the date of this letter.

 

If you should have any questions regarding the plan check comments, please email me at carolw@csgengr.com. All other questions, e.g. status, time frame, fee, etc. may be directed to the Community Risk Reduction Coordinator at (831) 685-6698.

 

CC:  File

As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source.  Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the Central Fire District of Santa Cruz County.