Fire Review |
|
Date: March
9, 2021 To: Rancho Del Mar Centers, LLC by Terramar Retail
Ctrs, LLC Applicant: Frank Wright Address: 1152 E. 7th. Ontario
CA 91764 From: Carol
Wallace, Plans Examiner Subject: Commercial
TI Address: 150
Rancho Del Mar Aptos CA
95003 APN: 039-221-11 (bldg.K) Permit: B-211539
The
Central Fire District has reviewed the plans for the above cited project and
the following corrections are required before approval can be obtained.
Please
add the appropriate NOTES, DETAILS and INFORMATION on your plans and RESUBMIT with an annotated copy of this
letter. All changes to drawings will
require "clouding of the change".
CORRECT on building plan application form
PLG200, the legal owner information showing Scott Grady. A later entry on Owner Agent Authorization
form PLG210, the owner and Rancho Del Mar Centers, LLC. Correct whichever to correct owner.
CORRECT on plans, page G-001, Required Agency
Approvals, from City of Aptos to Aptos/La Selva Fire Protection District.
ADD to plans, page G-001, Applicable Codes, and 2019 Aptos/La
Selva Fire Protection District Local Amendments.
NOTE on plans, page G-001 Deferred Submittals, that
modifications to the existing fire alarm system shall be deferred submittal. Aptos/La Selva Fire Protection District
Ordinance 1-19 requires a monitored fire alarm system in all commercial
structures. NOTE on plans, page G-001, that prior to making any alterations on
the fire alarm system, plans must be submitted for approval and permit issued. NOTE on the plans “the designer/installer shall submit two (2)
sets of plans and calculations for the Fire Alarm System to this agency for
approval.”
IDENTIFY
in the legend, or call out on plan, page A-301, the symbol for the fire
extinguisher. The extinguisher symbol
shown is not identified in a legend that I found.
CORRECT on the plans, page G-001, that address
numbers shall be a minimum of 6 inches, not 4 inches.
CORRECT on plans, page G-003, Door Notes, #2
rear address note referring to Long Beach Airport, and the reference to City of
Aptos to Aptos/La Selva Fire Protection District
REMOVE on plans, page G-003, Door Notes, #2
reference to multi-tenant bldgs. Not applicable to this plan submittal.
REMOVE on plans, page G-003, Door Notes, #4
reference to the Long Beach Muni Code (LBMC section….)
NOTE on the plans” the job copies of the building and fire
systems plans and permits must be on-site during inspections.”
Note: As a condition of submittal of these plans,
the submitter, designer and installer certify that these plans and details
comply with applicable Specifications, Standards, Codes and Ordinances, agree
that they are solely responsible for compliance with applicable Specifications,
Standards, Codes and Ordinances, and further agree to correct any deficiencies
noted by this review, subsequent review, inspection or other source, and, to
hold harmless and without prejudice, the reviewer and reviewing agency. Date: May 11, 2021 To: Rancho Del Mar Centers, LLC by Terramar Retail
Ctrs, LLC Applicant: Frank Wright Address: 1152 E. 7th. Ontario
CA 91764 From: Carol Wallace, Plans Examiner Subject: Commercial
TI Address: 150
Rancho Del Mar Aptos CA
95003 APN: 039-221-11 (bldg.K) Permit: B-211539
Based upon a review of the plans submitted, District
requirements appear to have been met, and PLANS ARE APPROVED FOR PERMIT.
The job copies of
the building and fire system plans and permits must be on-site during
inspection.
Please call the Community Risk Reduction Division to set
up an appointment when ready for an inspection. You will be asked for an
address and Assessor’s Parcel Number (APN).
A MINIMUM OF 48 HOURS NOTICE
to the Fire District is required prior to inspection.
Submit a check in the amount of $600.00 for this
particular plan check, made payable to Aptos Fire Protection District.
Mail to:
Community Risk Reduction 6934 Soquel Drive, Aptos, CA 95003
Fire District fees must be paid and a receipt for
District fees must be presented to the County Planning Department before
Building Permit issuance. A $75.00 late
fee may be added to your plan
check fees if payment is not received within 30 days of the date of this letter.
If you should have
any questions regarding the plan check comments, please email me at carolw@csgengr.com. All other questions, e.g. status,
time frame, fee, etc. may be directed to the Community Risk Reduction
Coordinator at (831) 685-6698.
CC: File As a condition of
submittal of these plans, the submitter, designer and installer certify that
these plans and details comply with applicable Specifications, Standards, Codes
and Ordinances, agree that they are solely responsible for compliance with
applicable Specifications, Standards, Codes and Ordinances, and further agree
to correct any deficiencies noted by this review, subsequent review, inspection
or other source. Further, the submitter,
designer, and installer agrees to hold harmless from any and all alleged claims
to have arisen from any compliance deficiencies, without prejudice, the
reviewer and the Central Fire District of Santa Cruz County. |