Sanitation Review

Review No:1
Sanitation District Review Comments: No. 1
Date of Review: 02-11-2021
Permit #: B-211539, APN: 039-221-11, Situs Address: 150 Rancho Del Mar Building K
This review was based on plans submitted for the subject project entitled Bruster’s Real Ice Cream prepared by Wright Design Studios dated 01-15-21.


Corrections Required:
1.) A sewer lateral video inspection was uploaded for this building on 08-12-2020. No repair requirements were issued at that time. (NO RESPONSE REQUIRED).
2.) Provide supplemental calculation showing estimated water consumption (in gal/day).
3.) Complete and return the Food Service Facility Wastewater Discharge Questionnaire: https://sccsd.wpcomstaging.com/wp-content/uploads/2020/07/Letterhead-fillable-FOOD-FACILITY-QUESTIONNAIRE-07-08-2020.pdf


Holds:
1.) The Sanitation Environmental Compliance Unit shall require that the existing grease interceptor be inspected. Call 831-477-3907.
2.) A fixture count inspection will be required.


Food Service Facility Operations /Commercial kitchens:
• All food service operations in the County of Santa Cruz are required to have a grease interceptor or trap to remove fats, oils, and grease from sanitary sewer water emanating from the kitchen prior to discharge.
• All sinks including mop sinks, floor sinks and floor drains must be routed through a grease interceptor/trap with the exception of bathroom drains and hand washing sinks (Some hand washing sinks will be required to be connected to the interceptor).
• Floor drains must be installed with screens that prevent solids from blocking the facility’s pipes and from entering the sanitary sewer.
• A dishwasher is not permitted unless a minimum exterior 350-gallon grease interceptor is installed.
• All grease traps will meet the Santa Cruz County Design Criteria. Grease trap sizing specifications are detailed in the design criteria. See the design criteria at http://www.dpw.co.santa-cruz.ca.us/environment.htm
• Grease additives or enzyme use in grease traps or lines, are not permitted unless they have been approved for use by the District.
• Garbage disposals are not allowed in commercial buildings.
• All lids to grease interceptor compartments and samples boxes must be kept clear and accessible at all time. No landscaping is permitted directly over the grease interceptor but may be present around the interceptor. If the proposed grease interceptor is set in landscaped areas, the lids must be set in concrete and raised above the ground surface to prevent sinking and prevent the lids from becoming covered with any eroded soil.
• All trash enclosures are required to have overhead coverage. If the trash enclosure has a drain it must be connected to the sanitary sewer. If an exterior grease interceptor is required, the drain must be routed through the grease interceptor. Drains routed to the sanitary sewer must be properly enclosed and covered to prevent storm water from entering the sanitary sewer. Storm drains are NOT permitted in trash bin enclosures.


Design and Construction Standards:
The project sewer design and connection of the project to the Santa Cruz County Sanitation District system will be required to conform to the County of Santa Cruz Design Criteria (CDC) Part 4, Sanitary Sewer Design, latest edition. (NO RESPONSE REQUIRED)
http://www.dpw.co.santa-cruz.ca.us/Portals/19/pdfs/DESIGNCRITERIA.pdf


Any questions regarding the above criteria should be directed to Bryan Wardlow of the Sanitation Engineering division at bryan.wardlow@santacruzcounty.us or (831) 454-2160.

Review No:2
Estimated water consumption (in gal/day) of 410 gpd provided by Wright Design Studios.

Food service questionnaire has been recorded by the Sanitation Environmental Compliance Unit.

No additional requirements at this time.


Inspections: 1.) ECU Inspection of grease traps. Call 831-477-3907.
2.) Final fixture count inspection. Call 831-454-2895.