Review No:11. The on-demand water heaters increase the gas demand significantly. Please provide a gas
line schematic that indicates BTU values of all existing and proposed gas appliances, the
developed length from the meter to each appliance outlet, the minimum pipe size and the
proposed gas pipe material. CPC 1216.0 and Table 1216.2(1)