Review No:1Responses must include an annotated copy of these comments and indicate the specific sheet/drawing
numbers where revisions are located. Text can be copied from the Application Status webpage and
pasted into a text editing program.
Please Respond: Have changes been made in addition to those resulting from the Building Review
Comments? ___________ (Yes or No). If yes, please briefly describe the additional changes and the
location on the plans/documents:
1. Please include wall, floor and ceiling assemblies. The required one hour assembly for walls and
floor/ceiling between units, STC min. 50 for airborne sound for walls and floor /ceiling between
units, and IIC minimum for floor/ceiling impact sound between units shall be maintained. These
provisions were required at the time of original construction. Existing conditions need to be
maintained.
CBC 420.2, 420.3, 1206.2, 1206.3
2. Please include specifications and/or details for plumbing penetrations through the repaired fire
partition wall. CBC 714.4
3. Please specify connections for the sistered floor joists.
4. Please specify shear wall material and nailing for the repaired wall to correspond with the report
recommendations.
Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or
http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx .
For eplan resubmittal requirements, please see
http://www.sccoplanning.com/PlanningHome/BuildingSafety/ePlanReview.aspx
Please be advised that if plan check comments are required to be addressed leading to a 3rd
plan check, additional charges will be added to your permit fee at an hourly rate.
If you have any questions regarding these building plan check comments, please contact
Laura Mellish at 831-454-3151 or email laura.mellish@santacruzcounty.us
|