B-222016 First Review 5/4/22 by JEH
1. C0.1: Please provide the engineer’s signature on the engineer’s stamp.
2. C0.1, C1.1: Please include the APN: 026-311-33 on the title block of the plan set.
3. C1.1: Please locate additional furnishings and equipment such as salon chairs to verify that the minimum 36-inch path of travel is maintained. CBC 11B-402
4. C1.1: Please note on the plans at the utility room that a minimum 32-inch clear path shall be maintained between the edge of the proposed countertop and the door jamb. CBC 11B-403.5.1 exception 1
5. C1.1: Please verify that accessible restroom signage is existing or detail required signage. CBC 11B-216, 11B-703
Note: For the referenced code information, go to http://www.bsc.ca.gov/Codes.aspx and/or http://www.sccoplanning.com/PlanningHome/BuildingSafety/BuildingCodes.aspx
This review is based on the 2019 California Codes, as adopted by Santa Cruz County. If you have any questions regarding these comments, please email jim.heaney@santacruzcounty.us .