EH Land Use Review

Review No:1

Onsite wastewater treatment system (OWTS) upgrade permit must be applied for and approved prior to approval of building permit application. 

Sewage disposal consultant to verify number of units proposed for garage remodel, report submitted for site evaluation is inconsistent.  Provide a floor plan for the garage remodel.

Proposed dispersal area for the OWTS must be fenced off during all construction activities and remain undisturbed.  Notes to the affect must be present on the building plans.


Review No:2


1.      Show the septic system, including tanks, leachfield and leachfield expansion area on any site plan pages, site improvement plan page C2.00, utilities sheet C6.02 and any drainage and grading plans. Also see #2 below for other notes required on these pages.

 

2.      Septic system areas including the tanks, leachfield and all leachfield expansion areas must be fenced off with temporary fencing during construction activities to prevent driving on and disturbance of the soil in these areas. Show this on any plan page that shows any parts of the septic system or drainage and grading plans, and utilities sheets. These areas must remain undisturbed. Disturbance of this area will result in the requirement for a revised OWTS design in an unaltered area, and additional testing and fees to prove the revised area meets standards.

 

3.      Trenching for electrical lines and cable, on pages E1.00 & E1.01, appears to run directly through the areas reserved for the leachfield expansion areas. These areas must remain undisturbed. Disturbance of this area will result in the requirement for a revised OWTS design in an unaltered area, and additional testing and fees to prove the revised area meets standards.

Review No:3

Approval by Environmental Health is pending other department approvals.