Fire Review |
|
Date: November 26, 2024 To: John & Gillian Montgomery, Owners Address: 1275 Glen Eyrie Ave. San Jose CA 95125 Applicant: Robin McCarthy, Architect, Arch Studio, Inc. Address: 1155 Meridian Ave., Ste 210 San Jose CA 95125 From: Carol Wallace, Plans Examiner Project Address: 106 Beachgate Way Aptos CA 95003 Subject: Demo Existing SFD & Construct New 2-Story SFD & Detached Garage APN: 038-213-12 Permit: APP-241060 / 738000207
We have reviewed plans for the above subject project and unfortunately,THE PLANS HAVE BEEN DENIED.
Please have the DESIGNER add appropriate NOTES and DETAILS showing this information andRESUBMIT plans, VIA COUNTY, with an annotated copy of this letter.
CORRECT on the plans, sheet GN-1, Fire Department Requirements:
· Note #1 – correct the code cycle from the 2019 to the 2022 code cycle andCentral Fire District amendments. · Note #2– correct the authority having jurisdiction from the San Jose Fire Department to the Central Fire District of Santa Cruz County. · Note #6– correct the required distance from the parcel from 250 feet to 400 feet from the hydrant to the furthest part of the proposed structure, for a sprinklered dwelling. · Note #10– correct fire access requirement from 200 feet to 150 feet from the public road to the furthest part of the proposed dwelling.
SHOW on the plan, the FIRE FLOW requirement for the subject property is 1000 gallons per minute for 120 minutes. NOTE on the plans the REQUIRED and AVAILABLE FIRE FLOW. The AVAILABLE FIRE FLOW information can be obtained from the Soquel Creek Water District.
NOTE on the plans that the designer/installer shall submit two (2) sets of plans, calculations, and cut sheets for the underground and overhead Residential Automatic Sprinkler System to this agency for approval. Installation shall follow our guide sheet. Cut sheets shall include, but not limited to piping, valves, gauges, and sprinkler heads.
NOTE on the plans that a 30-foot clearance will be maintained with non-combustible vegetation around all structures.
NOTE on the plan that job copies of the approved plans shall be on site for all inspections.
Should you have any questions regarding the plan check comments, please email me atcarolw@csgengr.com. All other inquires may be directed to Central Fire Districts Community Risk Reduction Division at (831) 685-6698.
CC: File & County
As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source. Further, the submitter, designer, and installer agree to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and the District. Date: 04/12/2025 Owner:
John & Gillian Montgomery Mailing
Address: 106 Beachgate Way, Aptos, CA Applicant: Robin McCarthy From: Central
Fire District of Santa Cruz County Project Address: 106
Beachgate Way, Aptos Subject: Montgomery Residence-SFD APN: 038-213-12 Permit/Eplan: APP-241060/738-000-207 Based upon review of the plans submitted, District requirements have been
met, and plans are approved for this permit.
The amount due
for this particular plan review is $1,196.74. $75.00 late fee may be added to your plan check fees
if payment is not received within 30
days of the date on the corresponding invoice.
To pay online,
please visit our District website at centralfiresc.org “Make a
Payment” (APN is required). Otherwise, check
payment shall be made payable to Central Fire District and either
dropped off or mailed to the address below. Community Risk Reduction 930 17th Avenue Santa
Cruz, CA
95062
Fire District fees must be paid, and a
receipt for District fees must be presented to the
Upon completion
of the above listed requirements, please call the Community Risk Reduction Division
to set up an appointment for an inspection. You will be asked for an address
and/or Assessors’ Parcel Number (APN). A minimum of 48 hours’ notice to the
Fire District is required prior to inspection. The job copies of the building
and fire system plans/permits must be on-site during inspection.
Should you have
any questions regarding the plan check comments, please email me at sconti@interwestgrp.com.
All other inquiries may be directed to Central
Fire Districts Community Risk Reduction Division at (831) 685-6698.
As a condition of submittal of these plans, the
submitter, designer and installer certify that these plans and details comply
with applicable Specifications, Standards, Codes and Ordinances, agree that
they are solely responsible for compliance with applicable Specifications,
Standards, Codes and Ordinances, and further agree to correct any deficiencies
noted by this review, subsequent review, inspection or other source. Further, the submitter, designer, and installer
agrees to hold harmless from any and all alleged claims to have arisen from any
compliance deficiencies, without prejudice, the reviewer and reviewing agency. |