Fire Review

Review No:1

Date: 4/14/25

Owner: Mike Shekoyan

Mailing Address: 4695 MacArthur Court #700, Newport Beach, CA

Applicant: Sabrina Hyman

From:   Central Fire District of Santa Cruz County

                               

Project Address: 122 Rancho Del Mar, Aptos, CA

Subject: Tenant Improvement – O’Reilly Auto Parts

APN:       039-221-11

Permit/Eplan: B-252469

           

 

Upon review of the plans for the above-cited project,the following corrections are required before approval can be obtained.  Please add the appropriate NOTES, DETAILS and INFORMATION on your plans andRESUBMIT with an annotated copy of this letter. All changes to drawings will require "clouding of the change".

Provide itemized responses to each of these comments. For questions on these comments please contact: [Andrew Hyatt, ahyatt@interwestgrp.com; 408.313.0876]

 

F1.       The plan set and sheet index include FP (fire sprinkler) sheets. However, the fire sprinkler system requires a separate permit and submittal. Revise the plans to state this. Also, revise the plans to remove these sheets or state “FOR REFERENCE ONLY”. CFC 903.1.

 

F2.       The plan set and sheet index include FA (fire alarm) sheets. However, the fire alarm system requires a separate permit and submittal. Revise the plans to state this. Also, revise the plans to remove these sheets or state “FOR REFERENCE ONLY”. CFC 907.1.

 

F3.       Sheet A0.1 has a HAZMAT INVENTORY STATEMENT note (see below). It states the HMIS will be under a separate cover. Provide approval from this Central Fire District for this as a separate cover. Otherwise, for all hazardous materials within the facility, provide an itemized list organized per the hazardous material classes for M-occupancies indicated in Table 5003.11.1 of the 2022 California Fire Code. For each hazardous material class, this list shall indicate the following information and the amounts for each hazardous material class shall be compared to the Maximum Allowable Quantities:

a.         Total amounts in storage.

b.         Total amounts in use – closed systems for each type of hazardous material class.

c.         Total amounts in use – open systems for each type of hazardous material class.

d.         Sizes of containers and tanks for each type of hazardous material class.

e.         Locations within the facility for each type of hazardous material class.

f.          Methods of storage and use for each type of hazardous material class.

A white label with black textAI-generated content may be incorrect.

 

F4.       Sheet A0.1. Revise the plans to show the locations of the portable fire extinguishers. CFC 906.1.

 

F5.       A2.2.2. NOTE on the plans “building numbers shall be provided.  Numbers shall be a minimum of six (6) inches in height on a contrasting background and visible from the street. Where numbers are not visible from the street, additional numbers shall be installed on a directional sign at the property driveway and the street.”

 

F6.       Revise the plans to show/paste each of the following, as applicable:

 

?NOTE on the plans “these plans are in compliance withCentral Fire Protection District Amendments.”

 

? As part of final approval, the fire alarm system will be required to be recertified by a licensed fire alarm company.  A copy will be provided to the agency of reference.

 

? Prior to making any alterations on the fire alarm system, plans must be submitted to the agency of reference for plan check and approval.

 

?NOTE on the plans” the job copies of the building and fire systems plans and permits must be on-site during inspections.”

 

If you should have any questions regarding the plan check comments, please email me atahyatt@interwestgrp.com.  All other inquiries may be directed to Central Fire Districts Community Risk Reduction Division at (831) 685-6698.

Note:  As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source, and, to hold harmless and without prejudice, the reviewer and reviewing agency.

 

Please reference our Standards/Regulations through Community Risk Reduction on our website atcentralfiresc.org      

 

 

Review No:2

Date:    7/9/25

Owner: Mike Shekoyan

Mailing Address: 4695 MacArthur Court #700, Newport Beach, CA

Applicant: Sabrina Hyman

From: Central Fire District of Santa Cruz County

                  

Project Address: 122 Rancho Del Mar, Aptos, CA

Subject: Tenant Improvement – O’Reilly Auto Parts

APN: 039-221-11

Permit/Eplan: B-252469                    

         

 

Based upon review of the plans submitted, District requirements have been met, and plans are approved for this permit.

 

The amount due for this plan review is $4,168.20. A $75.00 late fee may be added to your plan check fees if payment is not received within 30 days of the date on the corresponding invoice.

 

To pay online, please visit our District website at centralfiresc.org  “Make a Payment” (APN is required).

Otherwise, check payment shall be made payable to Central Fire District and either dropped off or mailed to the address below.

 

Community Risk Reduction

930 17th Avenue, Santa Cruz, CA  95062

 

Fire District fees must be paid, and receipt for District fees must be presented to the ?County Planning Department before Building Permit issuance.

 

Upon completion of the above listed requirements, please call the Community Risk Reduction Division to set up an appointment for an inspection. You will be asked for an address and/or Assessors’ Parcel Number (APN). A minimum of 48 hours’ notice to the Fire District is required prior to inspection. The job copies of the building and fire system plans/permits must be on-site during inspection.

 

 

Should you have any questions regarding the plan check comments, please email me at ahyatt@interwestgrp.com . All other inquiries may be directed to Central Fire Districts Community Risk Reduction Division at (831) 685-6698.

 

As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source.  Further, the submitter, designer, and installer agrees to hold harmless from any and all alleged claims to have arisen from any compliance deficiencies, without prejudice, the reviewer and reviewing agency.