Sanitation Review

Review No:1
Sanitation District Review Comments: No. 1
Date of Review: 09-26-2024
Permit #: B-245390, APN: 038-216-19, Situs Address: 347 Coates
This review was based on plans submitted for the subject project entitled [No Title] prepared by Craycroft Design dated 08-28-2024


Corrections Required:
1.) Per Sanitation District Code Section 7.04.375 A.3, a sewer lateral video inspection meeting district criteria must be submitted for review PRIOR to issuance of a building permit. The video inspection must include the entire private sewer system up to the connection to the public sewer main. Uploads shall be made to County Sanitation’s cloud storage platform (on www.box.com). 
County Sanitation staff shall review sewer lateral video inspection submittals and issue comments indicating repair requirements. Defects requiring repairs must be addressed as a part of this building permit. 
https://cdi.santacruzcountyca.gov/Portals/19/pdfs/Sanitation/Forms%20FAQs%20Laterals/LP%20Steps%20-%20AB2234.pdf
Sewer lateral video inspection criteria can be found at the following link:  https://cdi.santacruzcountyca.gov/Portals/19/pdfs/Sanitation/Forms%20FAQs%20Laterals/Video%20Submittal%20Criteria%20rev%2012-2023.pdf


2.) Please resubmit plans including any sewer lateral repair comments issued by County Sanitation staff (see plan check comment #1). Include the location of the required repairs on the site plans and notes indicating the details of the required sewer lateral repairs.
If no defects are found to be present in the sewer lateral, then this plan review comment shall be removed at the time of the next resubmittal.  


Design and Construction Standards: (no response required)
The project sewer design and connection of the project to the Santa Cruz County Sanitation District system will be required to conform to the County of Santa Cruz Design Criteria (CDC) Part 4, Sanitary Sewer Design, latest edition.  
https://cdi.santacruzcountyca.gov/Portals/35/CDI/PublicWorks/Transportation/2024DesignCriteria.pdf?rev=2024 


Any questions regarding the above criteria should be directed to Bryan Wardlow of the Sanitation Engineering division at bryan.wardlow@santacruzcounty.us or (831) 454-2160.
Review No:2
Sanitation District Review Comments: No. 2
Date of Review: 04-15-2025
Permit #: B-245390, APN: 038-216-19, Situs Address: 347 Coates
This review was based on plans submitted for the subject project entitled 347 Coates prepared by Craycroft Design dated 08-28-2024


Corrections Required:
Previously issued plan check comments not addressed. Comments repeated below:

1.) Per Sanitation District Code Section 7.04.375 A.3, a sewer lateral video inspection meeting district criteria must be submitted for review PRIOR to issuance of a building permit. The video inspection must include the entire private sewer system up to the connection to the public sewer main. Uploads shall be made to County Sanitation’s cloud storage platform (on www.box.com). 
County Sanitation staff shall review sewer lateral video inspection submittals and issue comments indicating repair requirements. Defects requiring repairs must be addressed as a part of this building permit. 
https://cdi.santacruzcountyca.gov/Portals/19/pdfs/Sanitation/Forms%20FAQs%20Laterals/LP%20Steps%20-%20AB2234.pdf
Sewer lateral video inspection criteria can be found at the following link:  https://cdi.santacruzcountyca.gov/Portals/19/pdfs/Sanitation/Forms%20FAQs%20Laterals/Video%20Submittal%20Criteria%20rev%2012-2023.pdf

2.) Please resubmit plans including any sewer lateral repair comments issued by County Sanitation staff (see plan check comment #1). Include the location of the required repairs on the site plans and notes indicating the details of the required sewer lateral repairs.
If no defects are found to be present in the sewer lateral, then this plan review comment shall be removed at the time of the next resubmittal.  


Design and Construction Standards: (no response required)
The project sewer design and connection of the project to the Santa Cruz County Sanitation District system will be required to conform to the County of Santa Cruz Design Criteria (CDC) Part 4, Sanitary Sewer Design, latest edition.  
https://cdi.santacruzcountyca.gov/Portals/35/CDI/PublicWorks/Transportation/2024DesignCriteria.pdf?rev=2024 


Any questions regarding the above criteria should be directed to Bryan Wardlow of the Sanitation Engineering division at bryan.wardlow@santacruzcounty.us or (831) 454-2160.
Review No:3
Sanitation District Review Comments: No. 3
Date of Review: 07-17-2025
Permit #: B-245390, APN: 038-216-19, Situs Address: 347 Coates
This review was based on plans submitted for the subject project entitled 347 Coates prepared by Craycroft Design dated 05-01-2025


Corrections Required:
Previously issued plan check comments not addressed. Comments repeated below:
1.) Per Sanitation District Code Section 7.04.375 A.3, a sewer lateral video inspection meeting district criteria must be submitted for review PRIOR to issuance of a building permit. The video inspection must include the entire private sewer system up to the connection to the public sewer main. Uploads shall be made to County Sanitation’s cloud storage platform (on www.box.com). 
County Sanitation staff shall review sewer lateral video inspection submittals and issue comments indicating repair requirements. Defects requiring repairs must be addressed as a part of this building permit. 
https://cdi.santacruzcountyca.gov/Portals/19/pdfs/Sanitation/Forms%20FAQs%20Laterals/LP%20Steps%20-%20AB2234.pdf
Sewer lateral video inspection criteria can be found at the following link:  https://cdi.santacruzcountyca.gov/Portals/19/pdfs/Sanitation/Forms%20FAQs%20Laterals/Video%20Submittal%20Criteria%20rev%2012-2023.pdf

2.) Please resubmit plans including any sewer lateral repair comments issued by County Sanitation staff (see plan check comment #1). Include the location of the required repairs on the site plans and notes indicating the details of the required sewer lateral repairs.
If no defects are found to be present in the sewer lateral, then this plan review comment shall be removed at the time of the next resubmittal.  

Design and Construction Standards: (no response required)
The project sewer design and connection of the project to the Santa Cruz County Sanitation District system will be required to conform to the County of Santa Cruz Design Criteria (CDC) Part 4, Sanitary Sewer Design, latest edition.  
https://cdi.santacruzcountyca.gov/Portals/35/CDI/PublicWorks/Transportation/2024DesignCriteria.pdf?rev=2024 


Any questions regarding the above criteria should be directed to Bryan Wardlow of the Sanitation Engineering division at bryan.wardlow@santacruzcounty.us or (831) 454-2160.