Building Review |
|
B-252469_2025-05-09_1st MRS Revise and harmonize documentation in a comprehensive
manner. If not otherwise noted, each comment refers to CBC 107.2. Building Review Comments 1.
Accessibility: See AB3002
Notice online. This project is NOT accessibility exempt (CBC Chapter 2,
11B-202.4, DOJ, DSA). Submit a completed
PLG-245
along with the detailed documentation identified on the form, and show all
related accessibility compliance upgrades on the plans. If noting on the form
that all existing elements meet 2022 code requirements, then show compliance
for all such items on the plans. For additional information, see this video
explaining Disabled
Access Upgrade Requirements for Existing Buildings and Facilities. Review
to follow. 2.
Sheet A/C=(A0.2.1, A2.2.2, C1, C2, C3, etc.):
Please harmonize architectural and civil for stairs, ramps, guards, handrails,
etc. A/C sheets cross reference each other for additional information but do
not show essential code compliance requirements. Documentation must clearly show
and harmonize related code compliance requirements and reference them in the
response letter (e.g. “see x/xx” rather than “see civil”). 3.
Sheet A/C: Please show the elevation heights for
finish floor, exterior upper and lower landings at pavement. Revise 1/C2 to
specify the number of treads instead of the approximation shown. 4.
Sheet A/C: Show ramp rise compliance; add an
intermediate landing if required. The rise for any ramp run shall be 30 inches
maximum. CBC 11B-405.6 5.
Sheet A/C: On both sides of the ramp, show
details for a curb or guide rail continuous along the length of the ramp. CBC
11B-303.5, 11B-405.9.2 6.
Sheet A/C: Show ramp width clearance compliance
between curb and/or guide rails. The clear width of a ramp run shall be 48
inches minimum. CBC 11B-405.5 7.
Sheet A/C: For door 100C, show on the plans a 42
inch or greater strike-side clearance to the top of the ramp run. CBC 11B-405.7.5 8.
Sheet A/C: Detectable warnings. The southern paved
area is a “vehicular way”, and the ramp circulation path requires a detectable
warning. The bollards shown on 3/A0.2.1 do not alleviate detectable warning
requirements, and while detail 8/A0.2.2 is marked “not used,” detectable
warnings are required. Show the location, layout with dimensions, and details
for a continuous 36” blended transition detectable warning between the required
ramp landing and the vehicular way. Detectable warnings are not allowed within
the ramp landing. CBC Chapter 2, 11B-250.1ex#1, 11B-247.1.2.5, 11B-302, 11B-405.7.1,
11B-705 9.
Sheet A/C: Detectable warnings. Show on the
plans that “Only approved DSA-AC detectable warning products and directional
surfaces shall be installed.” CBC 11B-705.3 10.
Item 92/C3: Show code compliance for stair
stripes. CBC 11B-504.4.1. 11.
Item 92/C3: Show code compliance for stair
nosing. CBC 11B-504.5. 12.
Sheet A/C: Guards are required at the open side
of walk surfaces >30-inches above any point within 36-inches of stairs and
ramps. Show complete details showing heights and openings. CBC 1015 13.
Sheet A/C: Show and harmonize locations of
handrails. Handrails shall be provided on both sides of stairs and ramps. CBC 11B-505.2 14.
Sheet A/C: Show complete details for top and
bottom handrail extensions at ramps. CBC 11B-505.10.1 15.
Sheet A/C: Show complete details for top and
bottom handrail extensions at stairs. CBC 11B-505.10.2, 11B-505.10.3 16.
Item 92/C3: Show the proposed protruding
handrail extensions to be 27-inches maximum above the finish floor or ground.
CBC 11B-307.4 17.
Sheet A/C: Show the top of gripping surface
height dimension above stairs and ramps. CBC 11B-505.4 18.
Sheet A/C: Show handrail clearance to walls,
guards and pilasters. CBC 11B-505.5 19.
Sheet A/C: Show handrail grip size and surface
requirements. Show attachment details. CBC 11B-505.7, 11B-505.8 20.
Item 92/C3: Clarify what concrete wall dimension
is 8-foot and specify the concrete thickness. 21.
Interior Elevations: Please mark references on
the plans showing orientation and drawing numbers. 22.
Interiors: Show requirements for the wall and
ceiling finish Class, flame spread index, and smoke developed index. CBC
803.1.2, Table 803.13 23.
Self-service shelving: Please indicate on the
plans if the 3-foot aisles serve elements on only one side or both sides. Aisles
serving both sides must be 44-inches or larger. Self-service shelves shall be
located on an accessible route complying with Section 11B-402. The clear width
for aisles shall be 36 inches minimum if serving elements on only one side, and
44 inches minimum if serving elements on both sides. CBC 11B-225.2.2, 11B-403.5.1ex4 24.
Self-service shelving: Storage racks are
proposed; complete structural details are required. For a general list of
standard rack/storage requirements, see the handout by the Gilroy
Storage Rack Guidelines, and provide all required information. SCC does not
have an exception for storage racks 5’-9” or less, so anchorage is still
required. 25.
Restrooms: The plumbing plans show all new
fixtures, piping, concrete floor removed/replaced, a hi/low drinking fountain
installed (which must be in alcove), etc. The architectural does not show this
scope and shows a fire extinguisher at the fountain location. If a fountain is
added, show CBC 11B-211 and 11B-602 compliance. Harmonize documentation and clearly
include all work in the project scope and coordinate with comment #1 above.
Review to follow. 26.
Restroom Door: Provide door signs. CBC
11B-216.8.1, 11B-703.7 27.
Special Inspections Form PLG240: Required
special inspections appear to include epoxy set holdowns, structural welds,
guard base welds, etc. The special inspector must be selected from the PLG-240
list of approved agencies. The project Engineer is required to identify
applicable CBC special inspections for the project on a completed PLG240 form
signed by all parties and incorporated onto the plan sheets. Forms &
Publications 28.
Sheet P0.1: Schedule shows WC 1.6 GPF max. Code
requires 1.28 max. CPC 411.2 29.
Sheet P0.1: Schedule M.V. remarks references which
is not included in the plans. 30.
Sheet P1.0: Seismic design references sheet G1.1
which does is not included in the plans. And refers to details that are
required but do not seem to be show for the water heater. Michael Sotero Certified Plans Examiner - Architect |
Tel: 831-454-3249 | michael.sotero@santacruzcountyca.gov B-252469_2025-07-15_2nd MRS Revise and harmonize documentation
in a comprehensive manner. If not cited below, see CBC 107.2. #X=previous
comment number (previous comment text online: Application Status) [KK:xxx] =
Kamus Keller response Note: The Civil
sheets were not bookmark creating additional review time. Responses often lack
clarity of the sheet and/or drawing where revisions are made. Additional review
fees are being added to the permit cost. Building Review Comments 1.
Red: The color red is not allowed. Revise all
sheets as required. (e.g. A0.2.1, A1.1, A2.2.1, A4.1, etc.) ePlan User Guide 2.
#1 Accessibility: [KK: The response conveys that no
hardship is requested.] Response: Understood, and since the project cost
exceeds the maximum valuation threshold, full compliance is mandatory. Please
correct the form items C1, C2, and C5 to all show zero. The fountain does not
exist and is simply required to be accessible when added; it is not an upgrade.
Similarly, the existing entry was already accessible, and the redesigned entry does
not contribute toward accessibly upgrades, it is simply a design choice that
must be accessible. Since full compliance is being demonstrated, once submitted
correctly the form will remain part of the issued documents. 3.
Full compliance is required, show accessible
electrical switch and outlet heights. CBC11B-308.1 4.
Sheet A4.1: Clarify that both restrooms must have
all-gender signage. California Health and Safety Code Section 118600 5.
Sheet A4.1, Unisex Restroom Doors: Show
privacy latch, a maximum operation force of 5 pounds, and all operable parts 34
inches minimum to 44 inches maximum above finished floor. Clarify if closers or
spring hinges are used, and specify closing speed requirements. CBC
11B-213.2.1, 11B-404.2.9, 11B-404.2.8 6.
Sheet A4.1: Elevation C show a 3’-4” vertical
dimension, clarify intent. 7.
#2, #3, #4 Sheet A/C: [KK: ramp is 28”. Rise shown on
elevation 3/A2.2.2.] Response: Drawing 3/A2.2.2 seems to show bottom of landing
at -27 inches and C2 shows the bottom of ramp at -29 inches. Harmonize
documentation. Previous Comment: Show ramp rise compliance;
add an intermediate landing if required. The rise for any ramp run shall be 30
inches maximum. CBC 11B-405.6 8.
#2, #5 Sheet A/C: [KK: This has been added. Handrail
design coordinated on both sets.] Response: Please clarify where revisions are
made in written responses as previously stated in comment #2. Comment #5 is not
about handrails it is about guide rails/curbs. Sheet C2 added a note “far rail
will need bottom guide rail: near rail can be attached to the guardrail.” which
does not explain requirements nor provide the required drawn details. Provide
drawn guide details that clearly demonstrate a 4 inch sphere cannot pass through,
a curb must be at least 6 inches above the walking surface at abrupt changes or
provide a guide centered between 2 inches and 4 inches, prevent wheel
entrapment, provide a continuous and uninterrupted barrier along the length of
the ramp and not reduce the ramp width to less than 48 inches clear. Address
the previous comment, review to follow. Previous comment: On
both sides of the ramp, show details for a curb or guide rail
continuous along the length of the ramp. CBC 11B-303.5, 11B-405.9.2 9.
#8 Sheet A/C: Detectable warnings. [KK: The
architect’s response differs to civil and detail 8/A0.2.2 remains marked “not
used.”] Response: Since this detail is not used, add the following to detail
PVMT-98/C3 “Detectable warning surfaces shall be yellow and approximate FS
33538 of SAE AMS-STD-595A.” CBC 11B-705.1.1.3.1 10.
#10 Item 92/C3: [KK: stair stripes requirement
note added to stair detail on sheet C3.] Response: Information added shows
incorrect stripe width, requires the dimension from nose of step/approach, and stripes
must be on the upper approach in addition to treads. “Exterior stairs shall
have the upper approach and all treads marked by a stripe providing clear
visual contrast. The stripe shall be a minimum of 2 inches wide to a maximum of
4 inches wide placed parallel to, and not more than 1 inch from, the nose of the
step or upper approach. The stripe shall extend the full width of the step or
upper approach and shall be of material that is at least as slip resistant as
the other treads of the stair. A painted stripe shall be acceptable. Grooves
shall not be used to satisfy this requirement.” CBC 11B-504.4.1 11.
#2, #12, #13 Sheet A/C: [KK: reference is made
to C2 and A2.2.2.] Response: The stairway is confusingly shown differently on drawings
and details, and this will affect both the layout and dimensions. Most sheets
show the top riser/landing aligned with grid A while A2.2.2 and PMVT-92 show
the upper landing extended beyond grid A (see comment below). It does not seem
possible to align riser with grid A as the details show risers with a sloped
face. Harmonize all documentation. CBC 1015, 11B-505.2 12.
#2, #12, #13 Grids on 2/A2.2.1 and 2/A2.2.2 are
labeled D-C-B but should be A-B-C. Harmonize documentation. 13.
#2, #15 Sheet A/C: [KK: top and bottom extension
added to stair detail.] Response: The bottom extension must specify the
dimension of 1 tread length between the stair nosing and the 1-foot horizontal
dimension. The horizontal dimension must be moved to the inside face of the
outermost vertical bar to align with code requirements. See comment below CBC 11B-505.10.2,
11B-505.10.3 14.
#2, #15 Sheet A/C: [KK: top and bottom extension
added to stair detail.] Response: As commented, the sharp corner shown at the
outer extension is not allowed, show a round/smooth transition as required by
code. Handrail gripping surfaces and any surfaces adjacent to them shall be
free of sharp or abrasive elements and shall have rounded edges. CBC 11B-505.8 15.
#2, #17 Sheet A/C: [KK: notes added to callouts
on sheet C2 as well as stair and handrail details C3.] Response: The civil
sheets confusingly incorrect terms calling handrails as ‘36” high guardrails.’
Revise notes for C2 stair and ramp, and C3 details to correctly identify
handrails and guardrails. CBC 11B-505.4 16.
#2, #17 Sheet A/C: [KK: notes added to callouts
on sheet C2 as well as stair and handrail details C3.] Response: As previously
commented, 1/C2 obscures handrail with a “METS” mark. Please make legible. 17.
#2, #19 Sheet A/C: [KK: grip size specifications
added to detail sheet C3.] Response: As previously commented, show attachment
details. Handrail to guardrail and handrail to wall attachments must resist
linear load of 50 pounds per foot and concentrated load of 200 pounds in
accordance with Section 4.5.1.2 of ASCE 7. CBC 1607.9.1, 1607.9.1.1 18.
#20 Item 92/C3: [KK: The wall is meant to say 8”
(thickness) concrete wall, this will be revised.” Response: The detail is not
revised to 8-inches; it still says 8-feet. Please address. 19.
#23 Area B shelving: [KK: Shelving located in
Parts Area ‘B’ is not self-storage (employee pull only).] Response: Label the
Area B as “Employee Work Area.” CBC 11B Chapter 2, 11B-403.5.1 Exception 4,
11B-248.1. 11B-248.2, 11B-203.9, 11B-206.2.8 20.
#23 Area B shelving: [KK: Shelving located in
Parts Area ‘B’ is not self-storage (employee pull only).] Response: Area B is
an “Employee Work Area” with “Common Use – Interior or exterior circulation
paths, rooms, spaces or elements that are not for public use and are made
available for the shared use of two or more people.” The aisles do not meet the
exception for “work area equipment” and must be “44 inches minimum if serving
elements on both sides.” Please address. CBC 11B Chapter 2, 11B-403.5.1
Exception 4, 11B-248.1. 11B-248.2, 11B-203.9, 11B-206.2.8 21.
#24 Shelving: [KK: Fixture calcs and details
provide as Supplemental Documentation]. Response: PLG-235 lists “Fixture Calculations”
but nothing is bookmarked nor was anything added. Please clarify, review to
follow. 22.
#29 Sheet P0.1: [KK: M.V. is noted on sheet P3.0
detail #3.] Response: Sheet P3.0 does not exist. Please revise. 23.
#30 Water Heater, Seismic: [KK: Seismic design
was left in by mistake and has been removed.] Response Detail 5/P2.0 “front
view” note references “sheet ME1” which does not exist and does not clearly
state that strapping is required. As previously commented, water heater seismic
strapping is required. Please correct notes and add strapping details to P2.0. CPC
507.2 Michael Sotero Certified Plans Examiner - Architect |