Building Review |
|
B-255420_2025-11-13_1st MRS Revise and harmonize documentation in a comprehensive
manner. If not cited below, see CRC R106.1 and/or CBC 107.2. Pending reviews of other agencies must be harmonized with
Building comments. Note: Aspects of sheets G-001 & G-002 or similar are not
proposed for installation, however, incorrect information cannot be shown.
Revise or remove as required. Building Review Comments 1.
Stamp/Sign: Inno Dez provides engineering and
must stamp/sign all sheets for mechanical, electrical, plumbing, and energy.
BPC 5536, 6735 2.
Sheet Information. Various sheets reference
details or sheets that are not included. Those sheet require a similar note of
purpose as shown at the upper left of A-001 or provide sheets/details. (e.g.
A-200) 3.
G-001: Note 402. States accessible “routs”
please revise. CBC 11B-402 4.
G-001: Drawing 2. Toilet paper dispenser as 12
inches max. Toilet paper dispensers shall comply with Section 11B-309.4 and
shall be 7 inches minimum and 9 inches maximum in front of the water closet
measured to the centerline of the dispenser. CBC 11B-604.7.1 5.
G-001: Drawings 3 and 4 do not show the correct
grab bar installation behind a toilet and the compartment doors are not how to
locate them. CBC 11B-604.5.2, 11B-604.8 6.
G-001: Drawing 5. Urinals can be 13- 1/2 minimum.
CBC 11B-605.2 Michael Sotero Certified Plans Examiner - Architect |