Building Review |
|
B-263780_2026-07-22_1st
Review by JAD Building Review Comments
1.
Sheet A0 – Name
and contact information of owner, architect/designer, engineer(s), and energy
consultant are missing, please create a Project Directory and add to sheet.
(PLG-280 D. 2)
2.
Sheet A0 – Under
current applicable building codes, please add “Santa Cruz County Code
Amendments”. (PLG-280 D. 6)
3.
Sheet A0 – Please
add Windows to List of deferred submittals. (See comment #X to understand if
windows need to be added to the list of deferred submittals). [PLG-280 D. 7]
4.
Sheet A0 – Cover
sheet is missing the ECC Features Summary from Energy Compliance Report. Please
add to the cover sheet. (PLG-280 D. 8)
5.
Architectural Sheets
– The renewal or expiration date is missing from the architectural stamp.
Please provide on all architectural stamped sheets. In accordance with BPC Section 5536.1,
documents stamped (sealed) and signed by an architect, must include the
expiration date of the architect’s license.
6.
Architectural Sheets
– Please specify under-floor ventilation method and minimum vent sizes, based
on 1 square foot of vents for 150 square feet of under-floor area. One vent opening shall be within 3’ of each
corner. Reduced vented area is permitted if a Class 1 vapor retarder is used.
Unvented crawl spaces are permitted if a vapor retarder and mechanical
ventilation or conditioned air is provided per CRC R408.3. (CRC R408.2)
7.
Sheet A1 – In
conversation with Elizabeth Hayward, the Mudroom can be labeled as a Hall without
having to remove the door. Because a garage cannot open into a bedroom per
code, the Mudroom needs to be recognized as something other than a bedroom.
Renaming the Mudroom to Hall avoids having to reduce the space to under 70 sq.
ft. (spaces under 70 sq. ft. are not recognized as a bedroom)
8.
Sheet A1 –
Insulation Requirements Box – Please update the last note in the box to call
out the required insulation per the CF1R (Title 24) report. R-xxx should be
filled in with the appropriate information.
9.
Sheet A1 – At
proposed remodeled areas where wall cavities may be exposed, unless existing
R-11 insulation is present, please specify minimum R-13 insulation for 2x4
walls and minimum R-20 insulation for 2x6 walls. Also, minimum R-19 raised floor insulation
and R-19 minimum roof insulation is required if these cavities are exposed due
to the remodel. [CEnC 150 and SC County Code 12.10.250(C)5.201.1.3]
10.
Sheet A1 – Please
specify the shower door size to allow minimum 22” clearance. (CPC 408.6)
11.
Sheet A1 – Please
indicate that the shower door enclosures shall have tempered safety glazing.
(CRC R308.4)
12.
Sheet A1 – Structural
plans show new crawl space accesses through foundation walls to the new
construction. Please locate a crawl space access that allows for access to
these new access spaces. (CRC R408.4)
13.
Sheet A1 – Please
provide the following note: Installation of Fireplaces, Decorative Gas
Appliances and Gas Logs When a fireplace is installed, it shall comply
with Section 110.5, Section 4.503 of Part 11, and shall have the following: 1. Closable metal or glass doors covering the
entire opening of the firebox; and 2. A combustion air intake to draw air from the
outside of the building, which is at least 6 square inches in area and is
equipped with a readily accessible, operable and tight-fitting damper or
combustion-air control device; and Exception to Section 150.0(e)2: An outside
combustion-air intake is not required if the fireplace will be installed over
concrete slab flooring and the fireplace will not be located on an exterior
wall. 3. A
flue damper with a readily accessible control. Exception to Section 150.0(e)3: When a gas
log, log lighter or decorative gas appliance is installed in a fireplace, the
flue damper shall be blocked open if required by the CMC or the manufacturer's
installation instructions. [CEnC 150.0(e)] PROHIBITED FEATURES Masonry or factory-built fireplaces: Pilot Light - Continuously burning pilot
lights are not allowed for indoor and outdoor fireplaces. Closable Doors - Masonry or factory-built
fireplaces must have a closable metal or glass door covering the entire opening
of the firebox. Combustion Intake - Masonry or factory-built
fireplaces must have a combustion outside air intake, which is at least six
square inches in area and is equipped with a readily accessible, operable, and
tight-fitting damper or combustion-air control device. Flue Damper - Masonry or factory-built
fireplaces must have a flue damper with a readily accessible control. Code Reference: 2025 Title 24, Part 6
Standards §150.0(e)
14.
Sheets A1 &
S3 – Please locate and specify minimum 22” by 30” attic access in each area
with readily accessible location to the attic spaces. Attic access is required
at areas that exceed 30 square feet and vertical height is 30” or greater,
measured from the top of the ceiling framing members to the underside of the
roof framing members. Attic access openings in walls shall be a minimum of 22”
wide by 30” high. [CRC R807.1] Please update the structural drawings to align
with the attic accesses in the architectural plans.
15.
Sheet A3 – Please
provide window manufacturer specifications to verify compliance with energy and
performance regulations or list this as a deferred submittal on the cover sheet
of the plan set. (2025 CA Energy Standards 110.6)
16.
Sheet MP1 – Please
provide details demonstrating compliance for special venting for island
fixtures for the proposed island sink. (CPC 909.1) Traps for island sinks and similar
equipment shall be roughed in above the floor and shall be permitted to be
vented by extending the vent as high as possible, but not less than
the drainboard height and then returning it downward and connecting it to the
horizontal sink drain immediately downstream from the
vertical fixture drain. The return vent shall be connected to
the horizontal drain through a wye-branch fitting and shall, in
addition, be provided with a foot vent taken off the vertical
fixture vent by means of a wye branch immediately below the
floor and extending to the nearest partition and then through the roof to the
open air, or shall be permitted to be connected to other vents at a
point not less than 6 inches (152 mm) above the flood-level rim of
the fixtures served. Drainage fittings shall be used on
the vent below the floor level, and a slope of not less
than 1/4 inch per foot (20.8 mm/m) back to
the drain shall be maintained. The return bend used under the
drainboard shall be a one-piece fitting or an assembly of a 45-degree (0.79
rad), a 90-degree (1.57 rad), and a 45-degree (0.79 rad) elbow in the order
named. Pipe sizing shall be as elsewhere required in this code. The
island sink drain, upstream of the returned vent, shall serve no
other fixtures. An accessible cleanout shall be installed in the
vertical portion of the foot vent.
17.
Sheet MP1 – The
gas pipe diagram is incomplete. Please remove the xxx filler text and provide
the proper sizing for the gas pipe. Please indicate BTU/hr values of all
existing and proposed gas appliances, the developed length from the meter to
each appliance outlet, the minimum pipe size and the proposed gas pipe
material. [CPC 1215.0 and Table 1215.2(1) or Table 1215.2(27) for propane]
18.
Sheets MP1 & A1
– The FAU note on sheet A1 calls out a new FAU unit. However, MP1 calls out for
the existing FAU to remain. Please correct the notes to agree with each other.
19.
Sheet E1 – Please
identify at least one island countertop receptacle for the first 9 sf of
countertop, and another receptacle for every additional 18 sf of
countertop. The location of the
receptacle may not be more than 12” below the countertop, or beneath a
countertop that extends more than 6” beyond the support base. [CEC 210.52(C)(2)]
20.
Sheet E1 – Please
locate at least one required GFCI protected receptacle for the garage. [CEC
210.8(B), 210.52(G)(1)] Ok to show an existing receptacle, please label with an
(e).
21.
Sheet E1 – Please
provide at least one GFCI protected receptacle in a waterproof enclosure,
accessible from grade level and not more than 6.5 ft. above grade at the front
and rear of the dwelling. [CEC 210.52 (E)(1), 210.8(A)(3), 406.9(B)(1)] This
requirement is missing at the Entry.
22.
Sheet E1 – The
200amp panel is called out on sheet A1. Please revise the electrical panel note
to include 200amp (to match A1).
23.
Supplemental
Documents – Please submit the fireplace manufacturer’s specifications or note
manufacturer and model number to verify the proposed fireplace conforms to the
listing requirements. If not selected at
this time, note the listed installation manual to be available at the jobsite. [CMC
302.1]
24.
Sheet S4 – Ridge
beam 1 is labeled as 4x10 on the structural plans. However, page 23 of the
structural calculations call for a 4x12 beam. Please update S4 to show a 4x12
ridge beam.
Jennifer Dye Plans Examiner | jennifer.dye@santacruzcountyca.gov |