B-264079_2026-08-10_1st Review by JAD

Building Review Comments

*  This plan check has not been reviewed by Zoning and other departments. Their comments may require changes that could impact the design of the project or the direction of Building comments. Please re-check the ePlan Review site to confirm all comments have been addressed before resubmitting.

 

1.            Sheet A100 – Please provide the following note on the plan:

The range hood shall meet or exceed either the minimum airflow in accordance with Table 150.0-E or the minimum capture efficiency in accordance with Table 150.0-E and Table 150.0-G. For an enclosed kitchen with a ____ (gas/electric) range in a dwelling unit >_____ sf (ex: 1500 sf), it shall have a CE of ____% or ____cfm (ex: 70% or 180 cfm). Capture efficiency ratings shall be determined in accordance with ASTM E3087 and listed in a product directory approved by the Energy Commission. Please note required inspection on the cover sheet.

Table

AI-generated content may be incorrect.

 

2.            Sheet A100 – Please locate the exhaust duct for the clothes dryer.  Unless manufacturer’s specifications allow for longer lengths, the duct length shall not exceed 14 feet, including two 90 degree elbows. A length of 2 feet shall be deducted for each 90 degree elbow in excess of two. [CMC 504.4.2.1]

 

3.            Sheet A100 – Please show existing and/or new lighting in the utility room.

 

Jennifer Dye Plans Examiner | jennifer.dye@santacruzcountyca.gov