Building Review

Review No:1

B-253190 First Review 7/11/25 by JEH

 

T-4: High strength bolting and post-installed bolting are identified as special inspection items on the plan set. In addition, 3,000 psi concrete is also a special inspection item.

Please complete the Special Inspection Form PLG-240. The engineer of record shall indicate required inspections.

You may download a copy of this form from our website at Forms & Publications (santacruzcountyca.gov) PLG-240

Note: Selected inspection agency must be pre-approved by the Building Official. Refer to the approved agency list at the end of the document. The special inspection document shall be printed on the plan sheets.

 

This review is based on the 2022 California Codes, as adopted by Santa Cruz County. If you have any questions regarding this comment please email jim.heaney@santacruzcountyca.gov