Review No:1 B-263989_2026-07-14_1st Review by JRW Building Review Comments - Please note, the proposed changes to the originally permitted pool are significant, and the submitted plans lack sufficient details and specifications for a complete review. Additional plan review and comments may be required upon resubmittal. [CRC R106.1.1]
- Please revise the plans and supporting documents to consistently reference the 2022 California Building Standards Code, under which the original permit was issued. The plans currently reference the 2025 code cycle, while the engineering and calculations were prepared under the 2022 code cycle. All documents must reference a single, coordinated code cycle. [CRC R106.1.1]
- Please add Santa Cruz County Amendments to the list of applicable codes. [CRC R106.1.1]
- Please submit a revised SUP file beginning with Form PLG-235. Include all revised consultant reviews, calculations, reports, and equipment specifications affected by the proposed changes as applicable. [CRC R106.1.1]
- Please provide complete manufacturer specifications, installation instructions, and listings for proposed equipment not previously approved under original permit. Remove remaining gas-piping and seismic gas-shutoff notes if no gas equipment is proposed. [CEnC 110.4, 110.5]
- Please revise the plans to provide consistent pool depths. Sheet PL-1 identifies a maximum pool depth of eight feet, while Sheet PL-2 identifies a maximum depth of six feet. Coordinate the plans, sections, structural design, excavation volume, pool volume, pump sizing, flow calculations, and equipment selections. [CRC R106.1.1] [CEnC 110.4, 150.0(p)]
- Please provide revised structural calculations or a written statement from the engineer of record confirming that the submitted structural sheets constitute the complete design for the revised pool shell, raised spa, Baja shelf, steps, raised bond beam, automatic-cover vault, and site conditions. Coordinate all reinforcement and detail references between Sheets PL-1, PL-2, 100, Detail 552, and Detail 672. [CBC1604.4, 1808.7.3] [SCCC 12.10.216(J)]
- Please provide the required pool deck or provide a site-specific engineering determination that the no-deck design satisfies County requirements for structural integrity and control of surface water and soil moisture. Show deck width, thickness, reinforcement, joints, sealant, positive drainage, and the required perimeter cutoff wall, as applicable. Santa Cruz County generally requires a four-foot-wide impervious deck around below-grade pools unless special engineering establishes that it is unnecessary. [SCCC 12.10.216(K)]
- Please provide a revised CF2R-PLB-03-E certificate demonstrating compliance with the updated pool design. Additionally, update the responsible builder information. [CEnC 110.4, 110.5, and 150.0(p)]
- Sheet PL-1 identifies existing four-foot-high vinyl fencing and gates to remain. The County requires the pool barrier to be at least 60 inches high, measured from the side facing away from the pool. Please revise the barrier design and show the height, maximum two-inch bottom clearance, allowable openings, non-climbable configuration, gate swing away from the pool, self-closing and self-latching operation, and compliant release location. Revise the note specifying a gate latch at 54 inches; the County generally requires the gate-release mechanism at least 60 inches above grade unless the approved pool-side release configuration is used.
[SCCC 12.10.216(C) through (E)]
John Williams Certified Plans Examiner | john.williams@santacruzcountyca.gov Review No:2B-263989_2026-10-01_2nd Review by JRW Building Review Comments - Please revise the structural engineering documents to consistently reflect the 2022 California Building Code, under which the original permit was issued. The submitted Detail 552 calculations identify the 2025 CBC as the design basis, and the Detail 672 calculations identify CBC 2024/IBC 2021. Provide revised calculations/details or written confirmation from the structural engineer that Details 552 and 672 are applicable to and comply with the 2022 CBC for this project. [CBC 1604.4]
- Please provide the final manufacturer, model number, specifications, installation instructions, and applicable listing information for proposed equipment not previously approved under the original permit. At a minimum, provide complete documentation for the proposed electric heat pump and automatic safety pool-cover system and coordinate the equipment identified on Sheet PL-3 with the submitted documents. [CEnC 110.4, 110.5; SCCC 12.10.216(F)]
- As previously requested, please provide the revised CF2R-PLB-03-E for the final pool design and update the responsible-builder information. The response letter states that the revised certificate is included in the SUP file; however, the certificate was not found in the submitted SUP package. [CEnC 110.4, 110.5, 150.0(p)]
John Williams Certified Plans Examiner | john.williams@santacruzcountyca.gov
|