Building Review

Review No:1

B-265456_2026-10-08_1st Review by JRW

Building Review Comments

  1. Please revise the electrical plans to provide consistent panel designations and greenhouse bay assignments. Sheet E-002 identifies Panel L1 serving Bay 5 and Panel L2 serving Bay 6, whereas Sheet E-401 identifies these panels as serving Bays 1 and 2, respectively. Additionally, clarify the renumbering of the previously approved panels serving Bays 2, 3, and 4 under permit B-261359. Coordinate the panel designations throughout the single-line diagram, panel schedules, and electrical layout plans. [CEC 110.22, 408.4(A)]
  2. Please submit a completed 2025 CEC-NRCC-PRC-E (Process Systems) Certificate of Compliance for the proposed horticultural lighting increase. Document the applicable horticultural lighting efficacy and control requirements, and coordinate the completed compliance documentation with the electrical plans. [CEnC 141.1(c)3, 120.6(h)5, 10-103]

John Williams Certified Plans Examiner | john.williams@santacruzcountyca.gov