Fire Review

Review No:1
Date: November 9, 2026
Applicant: Zak Hoyt
6443 SW Beaverton-Hillsdale Highway Suite 210 Portland OR

Project Address: 80 Rancho Del Mar Aptos, CA

Subject: New shelving for retail business electrical work for 16 new circuits
APN: 039-221-11
Permit/E-Plan: B-265454

Upon review of the plans for the above-cited project, the following corrections are required before approval can be obtained.

Please add the appropriate NOTES, DETAILS and INFORMATION on your plans and RESUBMIT with an annotated copy of this letter. All changes to drawings will require "clouding of the change".

This project, although noted as only for the purposes of structural for the new retail gondolas and updated electrical for the displays, the following items shall be addressed as this is a new tenant within the currently vacant retail space.
1. CORRECTION REQUIRED – ADD an exit plan to the plan set. As shown on the plans, it appears that inadequate secondary emergency exiting may be provided.
RESPONSE:

2. CORRECTION REQUIRED – SHOW the location of all fire extinguishers. Locations shall be in accordance with California Fire Code §906 etal..
RESPONSE:

3. CORRECTION REQUIRED – ADD NOTE Monitoring of the sprinkler system by a constantly attended location is required. As part of final approval, the fire alarm system will be required to be recertified by a licensed fire alarm company. A copy will be provided to the agency of reference.
RESPONSE:

4. CORRECTION REQUIRED – NOTE on the plans “building numbers shall be provided. Numbers shall be a minimum of six (6) inches in height on a contrasting background and visible from the street. Where numbers are not visible from the street, additional numbers shall be installed on a directional sign at the property driveway and the street.”
RESPONSE:

5. CORRECTION REQUIRED – NOTE on the plans” the job copies of the building and fire systems plans and permits must be on-site during inspections.”
RESPONSE:
 



If you have questions regarding plan check comments, please email me at   jimd@csgengr.com . For all other inquiries, please contact the Community Risk Reduction Division at (831) 685-6698.
Note: As a condition of submittal of these plans, the submitter, designer and installer certify that these plans and details comply with applicable Specifications, Standards, Codes and Ordinances, agree that they are solely responsible for compliance with applicable Specifications, Standards, Codes and Ordinances, and further agree to correct any deficiencies noted by this review, subsequent review, inspection or other source, and, to hold harmless and without prejudice, the reviewer and reviewing agency.

Please reference our Standards/Regulations through Community Risk Reduction on our website at centralfiresc.org